Hetzner logo

Hetzner Outage History

200 incidents recorded over the last 365 days, 188 of them resolved, 5 still open. Durations are measured from when PulsAPI first saw the problem to when it cleared, which is usually longer than the vendor's own figure.

Every Recorded Hetzner Incident

Hetzner incidents, newest first, with date, duration and status.
DateIncidentDurationStatus
Dec 2, 2026Maintenance work on Object Storage in FSNWe will perform planed maintenance work on our Object Storage. During this time, short connection interruptions may occur.12h 0mScheduled
Dec 2, 2026Maintenance work on Object Storage in HELWe will perform planed maintenance work on our Object Storage. During this time, short connection interruptions may occur.12h 0mScheduled
Dec 2, 2026Maintenance work on Object Storage in NBGWe will perform planed maintenance work on our Object Storage. During this time, short connection interruptions may occur.12h 0mScheduled
Nov 25, 2026UPS function tests in HEL1-DC1We will do routine function tests on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.8h 0mScheduled
Nov 25, 2026UPS function tests in HEL1-DC2We will do routine function tests on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.8h 0mScheduled
Nov 24, 2026Maintenance work on Object Storage in NBG, HEL and FSNDuring maintenance work on the clusters, we implemented an improvement to read and write loads, which is currently not compatible with older versions of Veeam; we are applying a patch for this, which may result in a…3h 53mResolved
Nov 24, 2026Issues with updating delegated nameservers & registrar status of DNS zonesThere are currently issues with updating the delegated nameservers & the registrar status of DNS zones.—Investigating
Nov 24, 2026Urgent maintenance of InferenceWe will perform urgent maintenance for the Inference experiment. During this maintenance period, Inference will not be available for a short time. We expect the downtime for Inference to last only a few minutes.4 minResolved
Nov 24, 2026Replacement of power supply components and UPS in NBG1-DC2During this time, technicians will be upgrading various power supply components, including the UPS system in NBG1-DC2 . The work should not negatively affect our server systems. You can see which data center your…12h 0mResolved
Nov 23, 2026Maintenance work on the webmail system (webmail.your-server.de)Due to maintenance work, our webmail system will be unavailable during this specified time period. This will affect the login at https://webmail.your-server.de, as well as ActiveSync for the managed server and web…2 minResolved
Nov 23, 2026Urgent maintenance on Object Storage in HEL+FSNTo ensure the stability and performance of our Object Storage in Helsinki (HEL) and Falkenstein (FSN), we are carrying out urgent maintenance work. During the maintenance, brief connection interruptions may occur. We…19h 56mResolved
Nov 23, 2026Maintenance UPS systems in HEL1-DC2We will perform routine maintenance work on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.56h 30mScheduled
Nov 23, 2026Maintenance UPS systems in HEL1-DC1We will perform routine maintenance work on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.56h 30mScheduled
Nov 19, 2026Announced Critical Security Vulnerabilities in PHPOn 18 November 2026, the PHP Security Team announced upcoming security updates intended, among other things, to address critical security vulnerabilities: https://www.php.net/archive/2026.php#2026-11-18-1 We are aware…32h 1mResolved
Nov 18, 2026Object Storage HEL: Creation of new buckets temporarily unavailableDue to strong growth in demand at our HEL location, it will temporarily not be possible to create new buckets at this location starting 19 November 2026, at 10:00 CET. Existing buckets are not affected and remain fully…—Investigating
Nov 18, 2026UPS function tests in HEL1-DC12We will do routine function tests on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.5h 17mResolved
Nov 18, 2026UPS function tests in HEL1-DC10We will do routine function tests on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.5h 16mResolved
Nov 18, 2026Fault report on Hetzner ConsoleDue to a fault the Hetzner Console is currently not available.36 minResolved
Nov 17, 2026Robot routine maintenance workDuring this time, we will be doing routine maintenance work on Robot. You will not have access to Robot or these other user interfaces: - Robot (https://robot.hetzner.com) - Robot Web Service…12 minResolved
Nov 17, 2026Hetzner Accounts routine maintenance workDuring this time, we will be doing routine maintenance work on Hetzner Accounts (https://accounts.hetzner.com). You will not have access to Hetzner Accounts or these other user interfaces: - Hetzner Console…12 minResolved
Nov 17, 2026Maintenance UPS systems in HEL1-DC12We will perform routine maintenance work on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.51h 46mResolved
Nov 17, 2026Maintenance UPS systems in HEL1-DC10We will perform routine maintenance work on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.55h 5mResolved
Nov 16, 2026Maintenance work on the webmail system (webmail.your-server.de)Due to maintenance work, our webmail system will be unavailable during this specified time period. This will affect the login at https://webmail.your-server.de, as well as ActiveSync for the managed server and web…2h 25mResolved
Nov 16, 2026Maintenance on cloud metricsWe are performing maintenance on the metrics for the cloud servers and load balancers. As a result, historical metrics for these services will be unavailable or only partially available.1h 0mResolved
Nov 15, 2026Maintenance work on billing functions and consumption dataDuring this time, we will be doing routine maintenance work which is why the following functions are temporarily not available: - Accounts - view/edit contact details - view/pay invoices - view transactions -…42 minResolved
Nov 14, 2026Object Storage in location fsn1 partially degradedObject Storage service in location fsn1 is currently only partially available. Requests to some buckets may fail or time out. We are currently investigating the issue.—Investigating
Nov 13, 2026API failure for metricsAPI endpoints for metrics (/servers/{id}/metrics and /load_balancers/{id}/metrics) are failing or data may be incomplete.4h 57mResolved
Nov 13, 2026Object Storage in location HEL partially degradedThe Object Storage service in location HEL is currently partially degraded. Write operations may take unexpectedly long or fail or time out. We are already working on fixing the issue and getting things back to normal.—Investigating
Nov 13, 2026Fault report on Cloud API and Hetzner ConsoleDue to a fault the Cloud API and the Hetzner Console are currently not available.38 minResolved
Nov 12, 2026API failure for metricsAPI endpoints for metrics (/servers/{id}/metrics and /load_balancers/{id}/metrics) are failing or data may be incomplete.1h 36mResolved
Nov 12, 2026Maintenance emergency power system in HEL1-DC8We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.7h 22mResolved
Nov 12, 2026Object Storage in location fsn1 partially degradedObject Storage service in location fsn1 is currently only partially available. Requests to some buckets may fail or time out. We are currently investigating the issue.32h 53mResolved
Nov 11, 2026API failure for metricsAPI endpoints for metrics (/servers/{id}/metrics and /load_balancers/{id}/metrics) are failing or data may be incomplete.2h 54mResolved
Nov 10, 2026UPS function tests in FSN1-DC1We will do routine function tests on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.45 minResolved
Nov 9, 2026Object Storage in location fsn1 partially degradedObject Storage service in location fsn1 is currently only partially available. Requests to some buckets may fail or time out. We are currently investigating the issue.5h 38mResolved
Nov 9, 2026Replacement of power supply components and UPS in NBG1-DC2During this time, technicians will be upgrading various power supply components, including the UPS system in NBG1-DC2 . The work should not negatively affect our server systems. You can see which data center your…57h 0mResolved
Nov 6, 2026Object Storage in location FSN1 partially degradedObject Storage service in location FSN1 is currently partially degraded. Requests to some buckets may fail or time out. We are currently investigating the issue.5h 50mResolved
Nov 5, 2026Maintenance work on mirror (mirror.hetzner.com / download.hetzner.com)In the mentioned period, we will perform maintenance work on the mirror (mirror.hetzner.com / download.hetzner.com), which may briefly lead to system updates being interrupted.1h 1mResolved
Nov 5, 2026Fault report on Hetzner ConsoleDue to a fault the Hetzner Console are currently not available.1h 2mResolved
Nov 4, 2026Cloud Router fault nbg1-cloud1-core_spine_rdev1We are currently experiencing a fault on our router nbg1-cloud1-core_spine_rdev1. Our technicians are working hard on analysing the cause of the interruption in order to solve the issue. Please bear with us. We…7 minResolved
Nov 4, 2026Urgent Maintenance work on the Server Monitoring System (SysMon)In the mentioned period, we will perform urgent maintenance work on the Server Monitoring System (SysMon), which will make it unavailable for a short time.15 minResolved
Nov 4, 2026Function tests on UPS and emergency power systems in FSN1-DC24We will do routine function tests on our UPS systems and on our emergency power system. Due to the redundant design of our power supply systems, we do not expect any issues.46h 7mResolved
Nov 4, 2026Outage of DHCP and Rescue Boot in FSN1We are investigating an outage of the DHCP in FSN1. Therefore, the rescue boot and installations via robot are currently unavailable. Our engineers are working on analysing the issue.7h 32mResolved
Nov 3, 2026Maintenance work on the webmail system (webmail.your-server.de)Due to maintenance work, our webmail system will be unavailable during this specified time period. This will affect the login at https://webmail.your-server.de, as well as ActiveSync for the managed server and web…36 minResolved
Nov 3, 2026Cloud Resource Creation DelayCurrently there is a delay in creating or modifying resources in the Hetzner Cloud.45 minResolved
Nov 3, 2026Fault report for Cloud DNS API and reverse DNS APIs (Primary IP, Floating IPs, Cloud Server, Load Balancer)We have encountered an issue with the Cloud DNS API and the reverse DNS APIs (Primary IPs, Floating IP, Cloud Server and Load Balancers)57 minResolved
Nov 3, 2026Load Balancers: Security relevant maintenance workWe will be performing routine maintenance work on Load Balancers in all locations. During this maintenance work, there may be a short connection loss from the active connections (TCP and HTTP) to the Load Balancers, or…14h 2mResolved
Nov 3, 2026Function tests on UPS and emergency power systems in FSN1-DC1We will do routine function tests on our UPS systems and on our emergency power system. Due to the redundant design of our power supply systems, we do not expect any issues.6h 41mResolved
Nov 3, 2026Maintenance work on abuse systemIn the mentioned period, we will be performing routine maintenance work on the abuse system. So we will not be able to process abuse tickets during that time, and you will not be able to use our abuse form.28 minResolved
Nov 2, 2026Maintenance UPS systems in FSN1-DC24We will perform routine maintenance work on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.6h 47mResolved
Oct 30, 2026Maintenance emergency power system in HEL1-DC1We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.4h 53mResolved
Oct 28, 2026DHCP degraded in FSN1 and NBG1The DHCP for FSN1 and NBG1 is not working as expected. This affects new installations in Robot, booting the Rescue System and dynamic IP configuration.26 minResolved
Oct 28, 2026CVE-2026-97631 - critical security vulnerability in the EDK II UEFI firmware componentA critical security vulnerability has recently been identified in the EDK II UEFI firmware component (CVE-2026-97631, CVSS 9.5). Further details can be found in the advisory…—Investigating
Oct 28, 2026UPS function tests in FSN1-DC8We will do routine function tests on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.25h 42mResolved
Oct 28, 2026Maintenance emergency power system in HEL1-DC1We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.4h 45mResolved
Oct 28, 2026UPS function tests in HEL1-DC6We will do routine function tests on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.1h 27mResolved
Oct 28, 2026Maintenance emergency power system in HEL1-DC2We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.4h 0mResolved
Oct 27, 2026Fault report on mirror (mirror.hetzner.de / download.hetzner.com / packages.hetzner.com)Due to a fault, there is currently limited/no availability to the mirror (mirror.hetzner.de / download.hetzner.com / packages.hetzner.com).1h 34mResolved
Oct 27, 2026Function tests on UPS and emergency power systems in FSN1-DC8We will do routine function tests on our UPS systems and on our emergency power system. Due to the redundant design of our power supply systems, we do not expect any issues.44 minResolved
Oct 27, 2026Maintenance UPS systems in HEL1-DC6We will perform routine maintenance work on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.25h 34mResolved
Oct 27, 2026Object Storage in location nbg1 partially degradedObject Storage service in location nbg1 is currently degraded. Requests may fail or time out. We are currently investigating the issue.2h 14mResolved
Oct 26, 2026Object Storage in location nbg1 partially degradedObject Storage service in location nbg1 is currently degraded. Requests may fail or time out. We are currently investigating the issue.2h 3mResolved
Oct 26, 2026UPS function tests in FSN1-DC13We will do routine function tests on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.53 minResolved
Oct 26, 2026API failure for metricsAPI endpoints for metrics (/servers/{id}/metrics and /load_balancers/{id}/metrics) are failing or data may be incomplete.46 minResolved
Oct 21, 2026PHP security issues CVE-2026-109618 and CVE-2026-109619The PHP versions we use are affected by the recently disclosed vulnerabilities CVE-2026-109618 and CVE-2026-109619. We will, of course, apply patches as soon as they become available. We are checking whether we can…172h 54mResolved
Oct 21, 2026Router fault fra-core8We are currently experiencing a fault on our router fra-core8. Our technicians are working hard on analyzing the cause of the interruption in order to solve the issue. Please bear with us. As soon as more information is…2h 17mResolved
Oct 21, 2026Urgent maintenance on vSwitch CloudNetwork connectorDuring the above-mentioned time frame, we will be carrying out urgent maintenance work on the network devices that connect vSwitches with Hetzner Cloud Networks. During this work we will implement some updates that…152h 45mResolved
Oct 21, 2026Maintenance UPS systems in HEL1-DC7We will perform routine maintenance work on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.27h 9mResolved
Oct 20, 2026Maintenance emergency power system in FSN1-DC22We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.2h 43mResolved
Oct 20, 2026Maintenance emergency power system in HEL1-DC2We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.26h 30mResolved
Oct 19, 2026Technical issues with vSwitch MAC learningMAC address information may not be installed correctly after MAC updates on some network devices. As a result, MAC learning within a vSwitch can be delayed, and ARP/NDP requests may go unanswered, which can lead to…34h 34mResolved
Oct 19, 2026Maintenance work on the webmail system (webmail.your-server.de)Due to maintenance work, our webmail system will be unavailable during this specified time period. This will affect the login at https://webmail.your-server.de, as well as ActiveSync for the managed server and web…32 minResolved
Oct 19, 2026Hetzner Accounts routine maintenance workDuring this time, we will be doing routine maintenance work on Hetzner Accounts (https://accounts.hetzner.com). You will not have access to Hetzner Accounts or these other user interfaces: - Hetzner Console…19 minResolved
Oct 19, 2026Robot routine maintenance workDuring this time, we will be doing routine maintenance work on Robot. You will not have access to Robot or these other user interfaces: - Robot (https://robot.hetzner.com) - Robot Web Service…19 minResolved
Oct 18, 2026Object Storage in location fsn1 degradedObject Storage service in location fsn1 is currently degraded. Requests may fail or time out. We are currently investigating the issue.21h 16mResolved
Oct 16, 2026CVE-2026-99999 (PwnEscape)On Thursday, October 15, 2026, a security vulnerability in the Linux kernel was disclosed. Shortly after this disclosure, a temporary mitigation was developed; it detects the attack vector at the system level and, based…245h 42mResolved
Oct 15, 2026Object Storage in location fsn1 degradedObject Storage service in location fsn1 is currently degraded. Requests may fail or time out. We are currently investigating the issue.18h 24mResolved
Oct 15, 2026Urgent maintenance on Load Balancers in NBG1During the specified time period, urgent maintenance work will be performed on the load balancers in NBG1. Unfortunately, it was not possible to provide advance notice. The load balancers will be unavailable for a short…21h 21mResolved
Oct 15, 2026Urgent maintenance on all core routersWe are currently carrying out urgent maintenance on all of our core routers. The routers are being serviced one after another. During this work, network redundancy is reduced globally. We do not expect any service…649h 37mResolved
Oct 15, 2026Failure of database serversWe are observing an unusual rate of failures on our database servers. This leads to our own websites as well as our customers database and websites on Managed Servers and Webhosting being not available temporarily. We…10h 12mResolved
Oct 15, 2026Maintenance work on abuse systemIn the mentioned period, we will be performing routine maintenance work on the abuse system. So we will not be able to process abuse tickets during that time, and you will not be able to use our abuse form.15 minResolved
Oct 14, 2026Fault report on Cloud API, Hetzner API and Hetzner ConsoleDue to an ongoing attack on our infrastructure the Cloud API (api.hetzner.cloud), Hetzner API (api.hetzner.com) and the Hetzner Console are currently partially unavailable.1h 26mResolved
Oct 14, 2026Maintenance emergency power system in HEL1-DC2We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.7h 11mResolved
Oct 13, 2026Cloud IPv6 routing problemsWe are currently experiencing a fault, which is preventing some cloud servers from being reached via IPv6. IPv4 traffic is unaffected. Our technicians are working hard on analysing the cause of the interruption in order…21h 36mResolved
Oct 13, 2026Load Balancers: maintenance workWe will be performing routine maintenance work on Load Balancers. During this maintenance work, there may be a short connection loss from the active connections (TCP and HTTP) to the Load Balancers, or from the Load…6h 27mResolved
Oct 13, 2026Maintenance emergency power system in HEL1-DC1We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.7h 59mResolved
Oct 11, 2026New vSwitch IP/MAC LimitsAs of 12.10.2026, the following vSwitch limits can no longer be exceeded: - A maximum of 256 MAC addresses per vSwitch - A maximum of 32 IP addresses per MAC address Please make sure that your setup does not need more…231h 13mResolved
Oct 11, 2026Object Storage in location FSN partially degradedThe Object Storage service in location FSN is currently degraded for some customers. Requests to download or upload objects may fail or time out. We are already working on fixing the issue and getting things back to…52 minResolved
Oct 8, 2026Fault report on recursive DNS servers at the locations HEL1, FSN1 and NBG1We currently see a raised response time of our recursive DNS servers at the locations HEL1, FSN1 and NBG1. You can find more information about our recursive DNS servers at…20h 19mResolved
Oct 8, 2026Increased Error Rate for Server Creation from One Click AppsWe've noticed an increased error rate when creating Cloud Servers from One Click Apps. Created servers remain stuck in the creation process or the creation ends in an error.5h 35mResolved
Oct 7, 2026Maintenance at backbone connection between NBG - FRAIn the above-mentioned period, maintenance will be performed at the backbone connection between NBG - FRA. This may lead to brief latency issues. We apologize for any inconvenience. Thank you for your understanding.11h 6mResolved
Oct 7, 2026Load Balancers: maintenance workWe will be performing routine maintenance work on Load Balancers. During this maintenance work, there may be a short connection loss from the active connections (TCP and HTTP) to the Load Balancers, or from the Load…4h 15mResolved
Oct 6, 2026Maintenance work on Object StorageWe will perform planed maintenance work on our Object Storage. During this time, short connection interruptions may occur.2h 15mResolved
Oct 6, 2026Fault report on Cloud API and Hetzner ConsoleDue to incorrect limit calculations, some actions (like creating ressources or moving a resource) were not working properly.0 minResolved
Oct 6, 2026Maintenance work on api.hetzner.comWe will be performing maintenance work on the infrastructure hosting api.hetzner.com. During this maintenance work, some requests to api.hetzner.com might not be answered successfully. Furthermore, some overviews in…23 minResolved
Oct 6, 2026Replacement of power supply components and UPS in FSN1-DC8During this time, technicians will be upgrading various power supply components, including the UPS system in FSN1-DC8 . The work should not negatively affect our server systems. You can see which data center your…72h 38mResolved
Oct 5, 2026The Deletion of Projects failsThe deletion of projects in Hetzner Console fails with an error.1h 11mResolved
Oct 5, 2026Replacement of power supply components at the substation / changes medium voltage in FSN1During this time, technicians will be upgrading various power supply components at the substation near our location in FSN1 . Background is the change of the medium voltage from 10 kV to 20 kV. The work should not…99h 0mResolved
Oct 2, 2026Load Balancers: Primary IP limits after Load Balancer transitionTo make the load balancer product more flexible in the future, we will convert the load balancer IP addresses to primary IPs. These will then be displayed separately from the load balancer in the Hetzner console and…94h 12mResolved
Oct 2, 2026Maintenance emergency power system in FSN1-DC13We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.5h 44mResolved
Oct 1, 2026Cloud Leaf fault nbg1-cloud1-leaf26We are currently experiencing a fault on our cloud leaf nbg1-cloud1-leaf26. Our technicians are working hard on analyzing the cause of the interruption in order to solve the issue. Please bear with us. As soon as more…22 minResolved
Oct 1, 2026Load Balancers: private network outage for dedicated serversThe Load Balancers are unable to reach dedicated server targets via the vSwitch connection due to the ongoing incident: https://status.hetzner.com/incident/288baeb9-5cb2-4e68-9074-b878dcd0d793.3h 47mResolved
Oct 1, 2026vSwitch issuesWe're currently seeing issues with the vSwitch. This can cause packet loss, higher latency or dropped connections between servers on a vSwitch. Our technicians are already working on it.23h 56mResolved
Oct 1, 2026UPS function tests in FSN1-DC21We will do routine function tests on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.9 minResolved
Oct 1, 2026Maintenance emergency power system in FSN1-DC7We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.8h 21mResolved
Oct 1, 2026Maintenance emergency power system in FSN1-DC4We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.8h 21mResolved
Oct 1, 2026UPS function tests in FSN1-DC19We will do routine function tests on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.8h 22mResolved
Sep 30, 2026Maintenance at backbone connection between NBG - FRAIn the above-mentioned period, maintenance will be performed at the backbone connection between NBG - FRA. This may lead to brief latency issues. We apologize for any inconvenience. Thank you for your understanding.7h 46mResolved
Sep 30, 2026Maintenance work on the webmail system (webmail.your-server.de)Due to maintenance work, our webmail system will be unavailable during this specified time period. This will affect the login at https://webmail.your-server.de, as well as ActiveSync for the managed server and web…16 minResolved
Sep 30, 2026Maintenance at nic.atThe .at registry (nic.at) will do routine maintenance work during the mentioned period. So you will not be able to order .at domains during that time.5h 50mResolved
Sep 30, 2026Function tests on UPS and emergency power systems in FSN1-DC21We will do routine function tests on our UPS systems and on our emergency power system. Due to the redundant design of our power supply systems, we do not expect any issues.18h 27mResolved
Sep 30, 2026Function tests on UPS and emergency power systems in FSN1-DC19We will do routine function tests on our UPS systems and on our emergency power system. Due to the redundant design of our power supply systems, we do not expect any issues.58 minResolved
Sep 30, 2026Maintenance emergency power system in FSN1-DC3We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.23h 26mResolved
Sep 30, 2026Maintenance emergency power system in FSN1-DC1We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.23h 26mResolved
Sep 30, 2026Maintenance at backbone connection between HEL - FRAIn the above-mentioned period, maintenance will be performed at the backbone connection between HEL - FRA. This may lead to brief latency issues. We apologize for any inconvenience. Thank you for your understanding.8h 20mResolved
Sep 30, 2026Maintenance emergency power system in HEL1-DC7We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.6h 46mResolved
Sep 29, 2026Maintenance emergency power system in FSN1-DC8We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.22h 37mResolved
Sep 29, 2026Maintenance emergency power system in FSN1-DC12We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.22h 36mResolved
Sep 29, 2026Maintenance emergency power system in HEL1-DC6We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.7h 11mResolved
Sep 28, 2026Object Storage in location HEL1 degradedThe Object Storage service in location HEL1 is currently degraded. Requests to download or upload objects may fail or time out. We are already working on fixing the issue and getting things back to normal.48 minResolved
Sep 24, 2026October billing run: One-time billing of outstanding amounts below €10We are currently preparing for the legally required introduction of e-invoicing. As a result, outstanding amounts below €10.00 / $10.00 must also be invoiced once in the upcoming billing run. Normally, such small…832h 8mResolved
Sep 24, 2026Maintenance work on abuse systemIn the mentioned period, we will be performing routine maintenance work on the abuse system. So we will not be able to process abuse tickets during that time, and you will not be able to use our abuse form.18 minResolved
Sep 22, 2026Newly created customer accounts can't create Cloud ServersWe've detected that newly created customer accounts after sign-up incorrectly have a Primary IP limit of 0. This prevents affected customers from creating Cloud Servers with Primary IPs. We're already working on a…19h 50mResolved
Sep 21, 2026Object Storage in location fsn1 degradedObject Storage service in location fsn1 is currently degraded. Requests may fail or time out. We are currently investigating the issue.4h 40mResolved
Sep 21, 2026Maintenance emergency power system in FSN1-DC6We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.26h 2mResolved
Sep 17, 2026UPS function tests in NBG1-DC3We will do routine function tests on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.41 minResolved
Sep 17, 2026Object Storage in location nbg1 degradedObject Storage service in location nbg1 is currently degraded. Requests may fail or time out. We are currently investigating the issue.1h 54mResolved
Sep 15, 2026Object Storage in location fsn1 for some buckets degradedWe are experiencing memory pressure on our systems that causes daemons to crash. For most requests no impact should be expected; But sometimes requests may be delayed or in rare cases aborted. We are investigating the…20h 53mResolved
Sep 15, 2026UPS function tests in NBG1-DC6We will do routine function tests on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.27h 19mResolved
Sep 14, 2026Function tests on UPS and emergency power systems in NBG1-DC6We will do routine function tests on our UPS systems and on our emergency power system. Due to the redundant design of our power supply systems, we do not expect any issues.47h 18mResolved
Sep 11, 2026Limited connectivity of Cloud servers on Cloud Leaf hil-cloud1-leaf8We are currently experiencing a limited connectivity on Cloud Servers on our cloud leaf hil-cloud1-leaf8. Our technicians are working hard on analyzing the cause of the interruption in order to solve the issue. Please…40h 0mResolved
Sep 11, 2026Load Balancers: maintenance workWe will be performing routine maintenance work on Load Balancers. During this maintenance work, there may be a short connection loss from the active connections (TCP and HTTP) to the Load Balancers, or from the Load…5h 2mResolved
Sep 10, 2026Fault report hetzner.comDue to a fault, the website https://www.hetzner.com is not or only partially accessible.1h 25mResolved
Sep 10, 2026Fault report for Hetzner AccountsThere is currently a fault on Hetzner Accounts (https://accounts.hetzner.com). For this reason, it is not possible right now to access to Hetzner Accounts or these other user interfaces: - Hetzner Console…1h 25mResolved
Sep 10, 2026Fault report for RobotThere is currently a fault on Robot that is affecting the following interfaces: - Robot (https://robot.hetzner.com) - Robot Web Service (https://robot-ws.your-server.de) - Robot Mobile - Robot Email Interface1h 25mResolved
Sep 10, 2026Maintenance work on the webmail system (webmail.your-server.de)Due to maintenance work, our webmail system will be unavailable during this specified time period. This will affect the login at https://webmail.your-server.de, as well as ActiveSync for the managed server and web…17 minResolved
Sep 9, 2026Robot routine maintenance workDuring this time, we will be doing routine maintenance work on Robot. You will not have access to Robot or these other user interfaces: - Robot (https://robot.hetzner.com) - Robot Web Service…12 minResolved
Sep 9, 2026Hetzner Accounts routine maintenance workDuring this time, we will be doing routine maintenance work on Hetzner Accounts (https://accounts.hetzner.com). You will not have access to Hetzner Accounts or these other user interfaces: - Hetzner Console…11 minResolved
Sep 9, 2026Object Storage in location HEL1 partially degradedWe are observing elevated response times and stalled requests for a subset of buckets.1033h 34mResolved
Sep 9, 2026Replacement of power supply components and UPS in FSN1-DC1During this time, technicians will be upgrading various power supply components, including the UPS system in FSN1-DC1 . The work should not negatively affect our server systems. You can see which data center your…7h 0mResolved
Sep 9, 2026Maintenance work Backbone/Core - FSN1During the above-mentioned time frame, we will be carrying out maintenance work on the backbone/core infrastructure in FSN1. During this work network traffic _won't_ be interrupted as redundant system will carry…8h 9mResolved
Sep 7, 2026Maintenance at backbone connection between FRA - HEL1In the above-mentioned period, maintenance will be performed at the backbone connection between FRA - HEL1. This may lead to brief latency issues. We apologize for any inconvenience. Thank you for your understanding.7h 50mResolved
Sep 7, 2026Maintenance UPS systems in HEL1-DC1We will perform routine maintenance work on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.2h 23mResolved
Sep 7, 2026Object Storage in location fsn1 degradedObject Storage service in location fsn1 is currently degraded. Requests may fail or time out. We are currently investigating the issue.3h 45mResolved
Sep 4, 2026Fault at DENICCurrently, there is a fault at the .de registry (DENIC). So you cannot order .de domains at the moment.1h 8mResolved
Sep 3, 2026UPS function tests in FSN1-DC18We will do routine function tests on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.1h 30mResolved
Sep 3, 2026UPS function tests in FSN1-DC20We will do routine function tests on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.2h 44mResolved
Sep 2, 2026Function tests on UPS and emergency power systems in FSN1-DC20We will do routine function tests on our UPS systems and on our emergency power system. Due to the redundant design of our power supply systems, we do not expect any issues.20h 44mResolved
Sep 2, 2026Maintenance work on Object Storage in NBG1We will perform planed maintenance work on our Object Storage. During this time, short connection interruptions may occur.2h 48mResolved
Sep 2, 2026Load Balancers: maintenance work in FSN & NBGWe will be performing routine maintenance work on Load Balancers in FSN & NBG. During this maintenance work, there may be a short connection loss from the active connections (TCP and HTTP) to the Load Balancers, or from…6h 22mResolved
Sep 2, 2026Load Balancers: maintenance work in all LocationsWe will be performing routine maintenance work on Load Balancers in all Locations. During this maintenance work, there may be a short connection loss from the active connections (TCP and HTTP) to the Load Balancers, or…4h 32mResolved
Aug 31, 2026Urgent maintenance on Load Balancers in FSN, NBG, and HELWe will perform urgent maintenance on the Load Balancers in FSN, NBG, and HEL. During this maintenance period, the Load Balancers will not be available for a short time. We expect the downtime for the Load Balancers…1h 31mResolved
Aug 28, 2026Telephone connection disruption - NBG1We are currently experiencing a disruption in the connection for our telephone support. Calls can be answered, but problems occur after approximately 30 seconds. Instead of calling support, please write a request using…2h 23mResolved
Aug 27, 2026Function tests on UPS and emergency power systems in FSN1-DC18We will do routine function tests on our UPS systems and on our emergency power system. Due to the redundant design of our power supply systems, we do not expect any issues.0 minResolved
Aug 27, 2026UPS function tests in FSN1-DC22We will do routine function tests on our UPS systems. Due to the redundant design of our power supply systems, we do not expect any issues.—Resolved
Aug 27, 2026Maintenance work on abuse systemIn the mentioned period, we will be performing routine maintenance work on the abuse system. So we will not be able to process abuse tickets during that time, and you will not be able to use our abuse form.20 minResolved
Aug 26, 2026Maintenance at backbone connection between NBG1 - FRAIn the above-mentioned period, maintenance will be performed at the backbone connection between NBG1 - FRA. This may lead to brief latency issues. We apologize for any inconvenience. Thank you for your understanding.38h 8mResolved
Aug 26, 2026Maintenance work on the webmail system (webmail.your-server.de)Due to maintenance work, our webmail system will be unavailable during this specified time period. This will affect the login at https://webmail.your-server.de, as well as ActiveSync for the managed server and web…3 minResolved
Aug 25, 2026Function tests on UPS and emergency power systems in FSN1-DC22We will do routine function tests on our UPS systems and on our emergency power system. Due to the redundant design of our power supply systems, we do not expect any issues.1h 0mResolved
Aug 25, 2026Object Storage in location NBG degradedDue to a hardware failure, the Object Storage Service is currently in a degraded state that requires urgent maintenance to prevent data loss. To speed up the recovery process, the Object Storage Service in NBG is…144h 56mResolved
Aug 25, 2026Load Balancers: maintenance work in HEL & HILWe will be performing routine maintenance work on Load Balancers in HEL & HIL. During this maintenance work, there may be a short connection loss from the active connections (TCP and HTTP) to the Load Balancers, or from…5h 5mResolved
Aug 24, 2026Object Storage in location nbg1 degradedObject Storage service in location nbg1 is currently degraded. Requests may fail or time out. We are currently investigating the issue.2h 4mResolved
Aug 24, 2026Function tests on UPS and emergency power systems in FSN1-DC24We will do routine function tests on our UPS systems and on our emergency power system. Due to the redundant design of our power supply systems, we do not expect any issues.1h 0mResolved
Aug 23, 2026Object Storage in location hel1 degradedObject Storage service in location hel1 is currently degraded. Requests may fail or time out. We are currently investigating the issue.2h 13mResolved
Aug 21, 2026Backbone connection fault between Frankfurt - HelsinkiWe are currently experiencing a fault in the backbone connection between Frankfurt - Helsinki. This may lead to brief latency issues. Please bear with us. As soon as more information is available, we will post it here…167h 44mResolved
Aug 21, 2026Limited availability of Cloud Volumes in Hillsboro (HIL)Due to the continuous high demand and the limited availability of the necessary hardware components, the provisioning and extending of cloud volumes at our Hillsboro (HIL) location is currently only possible to a…482h 14mResolved
Aug 20, 2026Object Storage in location hel1 degradedObject Storage service in location hel1 is currently degraded. Requests may fail or time out. We are currently investigating the issue.5h 18mResolved
Aug 20, 2026Maintenance work on billing functions and consumption dataDuring this time, we will be doing routine maintenance work which is why the following functions are temporarily not available: - Accounts - view/edit contact details - view/pay invoices - view transactions -…4 minResolved
Aug 19, 2026Load Balancers: maintenance work in ASH & HELWe will be performing routine maintenance work on Load Balancers in ASH & HEL. During this maintenance work, there may be a short connection loss from the active connections (TCP and HTTP) to the Load Balancers, or from…51h 31mResolved
Aug 19, 2026Load Balancers: maintenance work in SIN & HILWe will be performing routine maintenance work on Load Balancers in SIN & HIL. During this maintenance work, there may be a short connection loss from the active connections (TCP and HTTP) to the Load Balancers, or from…26h 3mResolved
Aug 18, 2026Maintenance work on mirror (mirror.hetzner.com / download.hetzner.com) - Location FSN1In the mentioned period, we will perform maintenance work on the mirror (mirror.hetzner.com / download.hetzner.com), which will make it unavailable for a short time. Consequently, system updates and resource downloads…54 minResolved
Aug 18, 2026Maintenance emergency power system in HEL1-DC3We will perform routine maintenance work on our emergency power systems. Due to the redundant design of our power supply systems, we do not expect any issues.146h 43mResolved
Aug 18, 2026Object Storage in location nbg1 degradedObject Storage service in location nbg1 is currently degraded. Requests may fail or time out. We are currently investigating the issue.3h 47mResolved
Aug 17, 2026Object Storage in location NBG degradedThe Object Storage service in location NBG is currently degraded. Requests to download or upload objects may fail or time out. We are already working on fixing the issue and getting things back to normal.1h 1mResolved
Aug 17, 2026Object Storage in location HEL degradedThe Object Storage service in location HEL is currently degraded. Requests to download or upload objects may fail or time out. We are already working on fixing the issue and getting things back to normal.2h 9mResolved
Aug 17, 2026Maintenance work on abuse systemIn the mentioned period, we will be performing routine maintenance work on the abuse system. So we will not be able to process abuse tickets during that time, and you will not be able to use our abuse form.23 minResolved
Aug 11, 2026Maintenance Hetzner Accounts (Invoices/Transactions)During this time, we will be doing routine maintenance work on Hetzner Accounts (https://accounts.hetzner.com). For this reason, the following features will not available: - Management of contact details - Invoice…37 minResolved
Aug 6, 2026Maintenance work on the webmail system (webmail.your-server.de)Due to maintenance work, our webmail system will be unavailable during this specified time period. This will affect the login at https://webmail.your-server.de, as well as ActiveSync for the managed server and web…1h 11mResolved
Aug 5, 2026Robot routine maintenance workDuring this time, we will be doing routine maintenance work on Robot. You will not have access to Robot or these other user interfaces: - Robot (https://robot.hetzner.com) - Robot Web Service…15 minResolved
Aug 5, 2026Hetzner Accounts routine maintenance workDuring this time, we will be doing routine maintenance work on Hetzner Accounts (https://accounts.hetzner.com). You will not have access to Hetzner Accounts or these other user interfaces: - Hetzner Console…15 minResolved
Aug 5, 2026Maintenance at DENICThe .de registry (DENIC) will do routine maintenance work during the mentioned period. So you will not be able to order .de domains during that time.27 minResolved
Aug 5, 2026Maintenance of Cloud Products (Firewalls, Private Networks, IPs, DNS)We are conducting a planned maintenance on Cloud products. Creating, changing, or deleting those products can be unavailable for a brief moment.2h 1mResolved
Aug 5, 2026Outage of DENIC servicesDENIC is currently experiencing a service disruption This may result in limitations when checking domain availability and when performing operations related to .de domains. Thank you for your understanding.1h 7mResolved
Aug 4, 2026Maintenance work on Object Storage in HEL1We will perform planed maintenance work on our Object Storage. During this time, short connection interruptions may occur.2h 25mResolved
Aug 4, 2026Maintenance work on Object Storage in NBG1We will perform planed maintenance work on our Object Storage. The goal is to increase the capacity in NBG1. During this time, short connection interruptions may occur.3h 18mResolved
Aug 4, 2026Maintenance work on Object Storage in FSN1We will perform planed maintenance work on our Object Storage. During this time, short connection interruptions may occur.3h 42mResolved
Aug 3, 2026Maintenance work on the webmail system (webmail.your-server.de)Due to maintenance work, our webmail system will be unavailable during this specified time period. This will affect the login at https://webmail.your-server.de, as well as ActiveSync for the managed server and web…5 minResolved
Aug 1, 2026Routing issue in our Europe backboneThere was a routing issue in our Europe backbone. This caused brief routing loops and packet loss. We apologize for the inconvenience. Thank you for your understanding.7 minResolved
Aug 1, 2026Object Storage in location fsn1 degradedObject Storage service in location fsn1 is currently degraded. Requests may fail or time out. We are currently investigating the issue.1h 55mResolved
Jul 30, 2026Temporary disruptions in traffic distribution across our authoritative DNS serversFor a brief period, there were disruptions in traffic distribution across our authoritative DNS servers. Some DNS queries were not resolved within the expected response time, which could temporarily result in higher…1h 35mResolved
Jul 29, 2026Cloud Leaf fault hel1-cloud1-leaf9We are currently experiencing a fault on our cloud leaf hel1-cloud1-leaf9. Our technicians are working hard on analyzing the cause of the interruption in order to solve the issue. Please bear with us. As soon as more…31h 14mResolved
Jul 29, 2026Cloud Leaf fault nbg1-cloud1-leaf97We are currently experiencing a fault on our cloud leaf nbg1-cloud1-leaf97. Our technicians are working hard on analyzing the cause of the interruption in order to solve the issue. Please bear with us. As soon as more…34h 12mResolved
Jul 29, 2026Maintenance work on mirror (mirror.hetzner.com / download.hetzner.com) - ASHIn the mentioned period, we will perform maintenance work on the mirror (mirror.hetzner.com / download.hetzner.com) in the region ASH, which may briefly lead to system updates being interrupted in that region.13 minResolved
Jul 28, 2026Maintenance at backbone connection between Frankfurt - HelsinkiIn the above-mentioned period, maintenance will be performed at the backbone connection between Frankfurt - Helsinki. This may lead to brief latency issues. We apologize for any inconvenience. Thank you for your…9h 59mResolved
Jul 28, 2026Cloud Resource Creation DelayCurrently there is a delay in creating or modifying resources in the Hetzner Cloud.1h 20mResolved
Jul 28, 2026Cloud Leaf fault hel1-cloud1-leaf16We are currently experiencing a fault on our cloud leaf hel1-cloud1-leaf16. Our technicians are working hard on analyzing the cause of the interruption in order to solve the issue. Please bear with us. As soon as more…1h 22mResolved
Jul 27, 2026Cloud Leaf fault fsn1-cloud2-leaf17We are currently experiencing a fault on our cloud leaf fsn1-cloud2-leaf17. Our technicians are working hard on analyzing the cause of the interruption in order to solve the issue. Please bear with us. As soon as more…15h 44mResolved
Jul 24, 2026Cloud Leaf fault nbg1-cloud1-leaf88We are currently experiencing a fault on our cloud leaf nbg1-cloud1-leaf88. Our technicians are working hard on analyzing the cause of the interruption in order to solve the issue. Please bear with us. As soon as more…247h 28mResolved
Jul 23, 2026Redirect from dns.hetzner.com to console.hetzner.com returns HTTP 404We are facing an unexpected behavior of our gateway which breaks the redirect from <a href="https://dns.hetzner.com" target="_blank" rel="noopener noreferrer">dns.hetzner.com</a> to <a href="https://console.hetzner.com"…271h 4mResolved
Jul 23, 2026Maintenance work on Object Storage in NBG1We will perform planed maintenance work on our Object Storage. During this time, short connection interruptions may occur.274h 4mResolved

Hear about the next one while it is open

Everything above is a record written after the fact. We can email you when the next Hetzner incident opens instead, at the point where knowing still changes what you do.

Free, no password, no card. Unsubscribe in one click.

How to Read This Hetzner Incident Log

Each row is an incident PulsAPI observed, not a summary written afterwards. The duration is wall-clock time between the first failing check and the first clean one, so it includes the window before Hetzner acknowledged anything. Vendor post-mortems typically measure from acknowledgement, which is why their numbers are usually shorter.

Incidents still open have no duration yet and are listed as ongoing rather than being given a running total. The archive covers the last 365 days; anything older has aged out of the window rather than never having happened.

The longest single Hetzner outage in this window ran 43d 1h, against a mean recovery of 1d 11h. If you depend on Hetzner in a customer-facing path, the longest figure is the one to design around. The mean is what happens on a normal bad day; the maximum is what happens on the worst one.